Pump cable size and voltage drop calculator

Give the supply, the motor current and the cable length from the board to the pump. It works out the voltage drop for each copper size and picks the smallest one within your limit.

Motor and cable

Leave 0 to estimate it from the kW.

The surface run plus the setting depth.

Result

Current used
-
Voltage drop, chosen size
-
Smallest copper size within the limit
-

Voltage drop by cable size
CopperDrop%

How the voltage drop is worked out

Every metre of cable has a little resistance, and the motor's current through it loses voltage on the way. The calculator uses the resistance of copper at a working temperature of about 70 °C (0.0206 Ω per metre for 1 mm²):

  • Single phase: drop = 2 × current × length × 0.0206 ÷ the cable size in mm² (out and back).
  • Three phase: drop = 1.73 × current × length × 0.0206 ÷ the cable size.

This is slightly on the safe side, because it ignores the power factor and the reactance of the cable. If you leave the current at 0, it is estimated from the motor size, assuming an efficiency and power factor typical of small submersible motors. The nameplate figure is always better.

Why it matters on a borehole

  • A submersible motor fed through too thin a cable starts slowly, runs hot and draws more current. That shortens its life and trips the protection.
  • The length is the whole run: from the board or the control box to the borehole head, and then down to the pump. A pump set at 100 m on a smallholding 150 m from the house is 250 m of cable.
  • The installation rules for South Africa (SANS 10142-1) limit the voltage drop between the supply point and the equipment; many pump makers ask for a lower drop for their motors. Ask the installer what limit they design to.
  • Joints under water must be made with a proper resin or heat-shrink splice kit, and flat drop cable is made for being in the water.

See pump control boxes for the protection and the wiring, and pump cable and pipe to price the cable.

Frequently asked questions

What size cable do I need for a borehole pump?
It depends on the motor current and the total cable length. A 0.75 kW single phase pump at 60 m may run on 1.5 or 2.5 mm², while the same pump 250 m from the board needs a much heavier cable. Use the calculator, then let the electrician confirm it.
Can I use ordinary house wire down the borehole?
No. Cable that hangs in the water must be made for it, such as flat submersible drop cable, with sealed splices at the motor lead.
Does three phase need thinner cable?
Usually, yes. For the same power, a three phase motor draws much less current per wire and the drop is smaller, which is one reason larger and deeper pumps are three phase.

More calculators and guides

Free quote request, no obligation

Request pump control boxes quotes

Fill in the duty sheet the way a pump technician would: how deep the water is, how high it must go, how much you need, or what has to be pumped away. Pump suppliers, installers and repairers in your area quote you directly.

Pump duty sheetPump Control Boxes
Request
71838
Logged
2026-11-21

1The job

2How many (optional, it helps the quote)

Your ordernot to scale

-
-
-
-
-
-
Estimate
-

A rule of thumb, not a pump selection.

3Power and timing

4Your list (optional)

  1. 01
  2. 02
Up to 12 lines: pumps, boxes, cable, pipe or spares.
Needs and options

5Your details

Free and no obligation. By sending you agree that we may share your request with suitable suppliers, installers and repairers. See our privacy policy.

Get free pump quotes